Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
169
Specifications
Chapter 6
Standards Compliance and Certifications
Standards Compliance
UL/CSA
EN/IEC
Other Agencies
UL 508 Industrial Control Equipment –
Suitable for Group Installation
CSA C22.2, No. 14
EN 60947-4-1 Low Voltage Switchgear
CE Marked per Low Voltage Directive 2006/95/EC
and EMC Directive 2004/108/EC
CCC (Pending)
KCC
C-Tick
ODVA for EtherNet/IP and DeviceNet
Certifications
cULus (File No. E3125, Guide NLDX, NLDX7)
Communication Ratings
Rated Insulation Voltage
250V
Operating Dielectric Withstand
UL/NEMA
: 1500V AC,
IEC
: 2000V AC
EtherNet/IP
EtherNet/IP ODVA – Conformance Testing
EtherNet/IP Interoperability Performance – Per A9 PF 2.1
Ethernet Communication Rate
10/100 Mbps, half or full-duplex
Ethernet Ports
2 (embedded switch)
Ethernet Network Topologies Supported
Star, Tree, Linear, and Ring
Device Level Ring Support
Beacon Performance, IEEE 1588 Transparent Clock
Ethernet Connector
M12, D code, female, with Ethernet keying, 4 Pin
Ethernet Cable
Category 5e: Shielded or unshielded
IP Configuration
Static, DHCP, or BootP
DHCP Timeout
30 s
Data
Transported over both TCP and UDP
Packet Rate (pps)
500 packets-per-second (2000 μs), Tx
500 packets-per-second (2000 μs), Rx
Consume Instance (Command)
Default of 3 words (Instance 150)
Produce Instance (Status)
Default of 14 words (Instance 152)
Message Support
Unicast or Multicast
Address Conflict Detection (ACD)
IP v4 Address Conflict Detection for EtherNet/IP devices
Sockets
150 maximum
Web Server
Security
Login and password configurable
Support Simple Mail Transfer Protocol (SMTP)
Webpage Features
Status, diagnostics, configuration
Concurrent Sessions
20
Web Server
HTTP 1.1
Network Connections
Concurrent TCP Connections
Maximum of 15 encapsulated messages over both TCP and UDP
Maximum I/O Connections (CIP Class 1)
Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or
listen-only]. One connection per PLC. Listen only connection requires a
data connection to be established.
Maximum Concurrent Explicit Messages (CIP Class 3)
6
Class 1 Connection API
2…3200 ms
Class 3 Connection API
100…10 000 ms
Request Packet Interval (RPI)
20 ms default (2 ms minimum)