164
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 5
Diagnostics
➊
In the case of a Disconnect open fault, reclosing the disconnect will cause a reset to be issued.
7
Yes
No
On
Parameter Sync
(PF
4M Codes 48, 71
and 81)
This fault is generated during the
parameter synchronization procedure
between the Control Module and the
internal drive when the syncing process
fails resulting in the drive configuration
not matching the Control Module
configuration.
1. The most common cause of this fault is that the
disconnect has been opened, or that power has
been removed from the drive. To clear the fault,
repower the drive and activate a reset.
2. The drive may have been commanded to default
values. Clear the fault or cycle power to the drive.
8
Drive
Controlled
No
On
DCBusOrDiscnnct
➊
(PF 4M Codes 3, 4
and 5)
This fault is a result of the drive’s Power
Loss
(PF 4M Code 3)
, UnderVoltage
(PF 4M
Code 4)
and OverVoltage
(PF 4M Code 5)
faults. When an Undervoltage occurs
because the Disconnect has been opened,
the condition will be diagnosed as an
“Open Disconnect” trip
1. The most common cause of this fault is that the
disconnect has been opened, or that power has
been removed from the drive. To Clear the fault,
repower the drive and activate a reset.
2. Monitor the incoming line for phase loss or line
imbalance, low voltage or line power interruption.
high line voltage or transient conditions. Bus
OverVoltage can also be caused by motor
regeneration.
3. Extending the [DecelTime1] Parameter 37 or
[DecelTime2] Parameter 70 may also help with this
fault.
9
Drive
Controlled
No
On
Stall Trip
(PF 4M Code 6)
During starting the motor did not reach
running speed within the prescribed
period. This fault occurs when the drive
detects a motor stall condition during
acceleration.
1. Check for source of stall (for example, excessive
load, or mechanical transmission component
failure).
2. Increase [AccelTime1] Parameter 36 or
[AccelTime2] Parameter 69 or reduce load so drive
output current does not exceed the current set by
[CurrentLimit] Parameter 31.
10
Drive
Controlled
No
On
Over Temperature
(PF 4M Code 8)
This fault occurs when the drive detects a
heat sink over temperature condition.
Check for blocked or dirty heat sink fins. Verify that
ambient temperature has not exceeded 40° C (104° F).
11
No
No
On
Ground Fault
(PF 4M Code 13)
This fault occurs a current path to earth
ground has been detected at one or more
of the drive output terminals.
Check the motor and external wiring to the drive
output terminals for a grounded condition.
12
No
No
On
Restart Retries
(PF 4M Code 33)
Drive unsuccessfully attempted to reset a
fault and resume running for the
programmed number of auto retries.
Correct the cause of the fault and manually clear.
Check [AutoRestartTries] Parameter 84 and
[AutoRestartDelay] Parameter 85 meets application
needs.
13
No
No
On
Drive Hardware Fault
Failure has been detected in the drive
power section.
1. Cycle power.
2. Replace unit if failure can not be cleared.
14
No
No
On
Output Short
This fault is generated when a hardware
output short circuit condition is detected.
Correct, isolate or remove wiring error prior to
restarting the system.
15
Yes
Yes
Off
User Defined
This fault is generated either in response
to the rising edge of user input 0...5,
[Input00Function...Input- 05Function]
Parameter 58...63.
This fault is generated based on user configuration.
This fault may be reset after the condition that caused
it is removed. For example, the Auxiliary Input goes
low or the DeviceLogix logic drives the bit low.
16
No
No
On
Hardware Fault Trip
This fault indicates that a serious
hardware problem exists. This fault is
generated when either the PF 4M drive is
not detected or an invalid factory
configuration setting is detected.
Power cycle to correct. If fault persists the ArmorStart
LT requires replacement.
Table 29 - Fault LED Indicator for Bulletin 294E
Blink
Pattern
Auto-Reset
Capable
Disable
Default
Bulletin 294E
Trip Status
Description
Action
Summary of Contents for ArmorStart 290E
Page 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Page 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Page 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Page 251: ......