Rockwell Automation Publication 825-UM004D-EN-P - April 2012
191
Specifications
Chapter
A
Primary Current
Transformers
➊
Designation according to IEC 60044 part 2:
825-CBCT Core Balance
Current Transformer
Minimum Nominal Operating Voltage
Nominal Operating Voltage of Motor
Minimum Rated Primary Current
l
1n
Nominal Operating Current of Motor
Rated Secondary Current [A]
825-MCM2
825-MCM5
825-MCM20
1
25
5
Class and Nominal Overcurrent Protection
5P10 ext. 120%
➊
Power Rating
According to power consumption in leads and measuring circuit.
Rated Frequency
50/60 Hz
Burden
825-MCM2
825-MCM5
825-MCM20
Power Consumption at Maximum Rated Current
[VA/phase]
0.1
0.2
0.4
Continuous Thermal Current [A]
3
6
24
Thermal Current, 1 s Duration [A]
250
400
600
No Load
An open-circuit secondary is permitted, as the burden is provided
in the converter module circuitry.
5
Total Measurement Error (percentage):
± 5% within range up to rated nominal overcurrent
± 1% at rated nominal primary current
P
For Protection Purposes
10
Rated Nominal Overcurrent Factor:
10X rated nominal primary current
ext.
120%
Extended Rated Thermal Current:
120% of rated nominal primary current (if
l
e
motor > 87%
of rated nominal transformer current)
Ratio
100:1
Current Range
0.5...10 A
Continuous Thermal Current
0.5 A
Saturation Current
30 A
Thermal Current, 1 s Duration
25 A
Rated Burden at Maximum Rated Current
0.4 V A
Rated Frequency
50/60 Hz
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......