825-PDN DeviceNet Communication Card
Setting the Hardware Switches
Use the following steps to commission the card:
1.
Set the node address switches.
Figure 41 - Node Address and Data Rate Setting Switches
Table 53 - Node Address MAC ID Setting
Switch Setting
Description
0…63
Node address setting determined by switch values when set in this range.
•
MSD = most significant digit
•
LSD = least significant digit
64…99
For switch settings in this range, node address setting is determined by the
software setting using the RSNetWorx for DeviceNet configuration tool.
99
Factory default setting.