Rockwell Automation Publication 825-UM004D-EN-P - April 2012
189
Specifications
Chapter
A
Mechanical Ratings
RTD Scanner Module
Environmental
Ambient Temperature
Storage: -40…+85°C (-40…+185°F)
Operating (open): -20…+60°C (-4…+140°F)
Humidity (Operating)
5…95% Non-condensing
Maximum Altitude
2000 m
Vibration (per IEC 68-2-6)
3 G
Shock (per IEC 68-2-27)
30 G
Control Terminals
Terminal Screw
M3
Cross Section (1 wire, stranded/solid)
0.14…2.5 mm
2
/#20…12 AWG
Torque
0.79 N•m/7lb-in
Degree of Protection
IP20
Ground Screw
Terminal Screw
#6
Torque
1.4 N•m/12 Lb-in
Supply
Rated Supply Voltage
U
s
110/240V AC
Operating Range
0.80…1.2
U
s
Rated Frequency
50/60 Hz ± 5 Hz
Max. Power Consumption
5 VA
Rated Insulation Voltage
U
i
300V AC
Rated Impulse Strength
U
imp
4kV
Pollution Degree
2
Environmental
Ambient Temperature Storage
Storage: -40…+85°C (-40…+185°F)
Operating: -20…+60°C (-4…+140°F)
Humidity (Operating)
5…95% Non-condensing
Maximum Altitude
2000 m
Vibration (per IEC 68-2-6)
3G
Shock (per IEC 68-2-27)
30G
Inputs
Number of input channels
12
Type
3-wire
Compatibility
CU10, NI100, NI120, PT100 (per IEC 60751: 1983)
Range
-50…250°C
Accuracy
± 2°C
Open Circuit Detection
> 250°C
Short Circuit Detection
< -50°C
Control Terminals
Terminal Screw
M3
Cross Section (1 wire, stranded/solid)
0.25…2.5mm
2
(24…12 AWG)
Torque
0.4…0.6 Nm (3.5…5.3 Lb-in)
Degree of Protection
1P20
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......