Chapter 6
Configuring Protection & Logic Functions
The relay asserts the Emergency Restart bit in response to any of the following
conditions:
•
the control input assigned to Emergency Restart asserts.
•
the relay receives a network Emergency Restart control command.
When the Emergency Restart bit asserts, the relay does the following:
•
Resets the motor thermal element capacity used to 0%.
•
Manipulates the Starts-Per-Hour, Minimum Time Between Starts, and
Anti-backspin functions to permit an immediate start.
•
De-asserts the Trip output contact if a fault detecting element is not
picked up.
•
Initiates a motor start.