134
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 10
Modbus RTU Communications
Figure 47 - Example of Modbus network consisting of a MicroLogix 1500 PLC as the Master device
and an 825-P and PanelView 550 as the Slave devices.
Commissioning
The Modbus communication card (Port 4) can be configured through
the front panel or serial port using the following settings. Front panel
access uses the following path:
MAIN > Set/Show > Port > Port 4
Table 63 - Modbus communication card settings
The following table provides settings to use for each communication card:
Table 64 - Communication card settings
Setting Prompt
Setting Range
Factory Default
COMM INTERFACE
232, 485
232
PROTOCOL
ASC, MOD
MOD
SPEED
300 … 38,400 bps
19,200
PARITY
O, E, N
N
MODBUS SLAVE ID
1 … 248
248
Setting Prompt
Setting Range
DeviceNet
Modbus
Empty
COMM INTERFACE
232, 485
232
232
232
PROTOCOL
ASC, MOD
MOD
MOD
MOD
SPEED
300 … 38,400 bps
19,200
19,200
19,200
PARITY
O, E, N
N
N
N
MODBUS SLAVE ID
1 … 248
248
1 to 247
1
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......