Rockwell Automation Publication 825-UM004D-EN-P - November 2012
139
Modbus RTU Communications
Chapter
10
The relay responses to errors in the query are shown below:
Table 73 - 10h Preset Multiple Registers Query Error Messages
60h Read Parameter
Information Command
The 825-P uses this function to allow a Modbus master to read parameter
information from the relay. One parameter (setting) is read in each query.
Table 74 - 60h Read Parameter Information Command
The Parameter Descriptor field is defined in Table 75:
2 bytes
Starting Address
2 bytes
Number of Registers
2 bytes
CRC-16
Error
Error Code Returned
Communication Counter
Increments
Illegal register to set
Illegal Data Address (02h)
Invalid Address
Illegal Write
Illegal number of registers to set
Illegal Data Value (03h)
Illegal Write
Incorrect number of bytes in
query data region
Illegal Data Value (03h)
Bad Packet Format
Illegal Write
Invalid register data value
Illegal Data Value (03h)
Illegal Write
Bytes
Field
Bytes
Field
Requests from the master must have the following format:
1 byte
Slave Address
1 byte
Function Code (60h)
2 bytes
Parameter Number
2 bytes
CRC-16
A successful response from the slave will have the following format:
1 byte
Slave Address
1 byte
Function Code (60h)
2 bytes
Parameter Number
1 byte
Parameter Descriptor
1 byte
Parameter Conversion
2 bytes
Parameter Minimum Settable Value
2 bytes
Parameter Maximum Settable Value
2 bytes
Parameter Default Value
2 bytes
CRC-16
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......