210
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter B
Parameter List
I/O Settings
292
40193
400193
ANALOG OUT SEL
0 = Load_I
0
—
—
Get/Set
1 = %Therm
2 = Wdg_RTD
3 = Brg_RTD
4 = PF
5 = Pwr_kW
6 = Avg_I
7 = Max_I
293
40194
400194
TRIP INHIBIT
0 = Curr.Imbalance
0
—
—
Get/Set
1 = Jam
0
2 = Ground Fault
0
3 = Short Circuit
0
4 = Undercurrent
0
5 = Start Inhibit
0
6 = PTC
0
7 = RTD
0
294
40195
400195
RELAY BEHAVIOR
0 = Trip Fail-Safe
1
—
—
Get/Set
1 = Aux1 Fail-Safe
1
2 = Aux2 Fail-Safe
1
3 = Aux3 Fail-Safe
1
4 = Aux4 Fail-Safe
1
5 = Aux5 Fail-Safe
1
6 = Aux6 Fail-Safe
1
Timer
Settings
295
40196
400196
ON DELAY T1
0
240
0
1
s
Get/Set
296
40197
400197
OFF DELAY T1
0
240
0
1
s
Get/Set
297
40198
400198
ON DELAY T2
0
240
0
1
s
Get/Set
298
40199
400199
OFF DELAY T2
0
240
0
1
s
Get/Set
Front Panel
Set
299
40200
400200
LCD TIMEOUT
0 = Off
30
0
1
min
Get/Set
300
40201
400201
LCD CONTRAST
1
8
0
1
—
Get/Set
301
40202
400202
DISPLAY ENABLE
0 = Time & Date
0
—
—
Get/Set
1 = Ground Current
0
2 = Curr. Imbalance
0
3 = Frequency
0
4 = Therm Cap Used
0
5 = Volt Imbalance
0
6 = Power
0
7 = RTD Temp
0
Group
DeviceNet
Param No.
Modbus Register
Parameter Name
Min
Max
Default
Scale
Factor
Units
Access
Read (0x03h)
Write (0x06h)
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......