Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
54
Line Interface Module
Table 33 - Power Dissipation Specifications
Fuse Specifications
Use Class CC, J, L, or R fuses with current rating as indicated in the table below.
The table below lists fuse examples recommended for use with 2094-AL09 and
2094-BL02 line interface modules.
Table 34 - Fuse Specifications
Cat. No.
Dissipation at 100% of Rated Power Output
(watts)
2094-AL09
72
2094-AL
xx
S
52.5
2094-BL02
90
2094-BL
xx
S
42.9
2094-XL75S-C
x
52.5
IMPORTANT
The 2094-AL
xx
S, 2094-BL
xx
S, and 2094-XL75S-C
x
line interface modules provide
branch-circuit protection. Follow all applicable NEC and local codes.
Cat. No.
VAC Input Power Fuse
(2)
(2) Part numbers shown are examples of Bussmann fuses.
2094-AL09
(1)
(1) The maximum short circuit current available from the source must
be limited to 5000 A.
KTK-R-25 (25 A)
2094-BL02
(2)
KTK-R-30 (30 A)
ATTENTION:
Bulletin 1492 and 140M circuit breakers should not be used on the output
of an AC drive as an isolating disconnect switch or motor overload device. These devices
are designed to operate on sine-wave voltage and the drive’s PWM waveform does not
allow it to operate properly. As a result, damage to the device will occur.