Line Interface Module
Figure 28 - Wiring Requirements
(catalog numbers 2094-AL09 and 2094-BL02)
Cat. No.
Description
Connects to Terminals
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
2094-AL09
(230V)
VAC LINE
IPL-1
IPL-2
IPL-3
IPL-4
2.5
(14)
10.0
(0.38)
0.5…0.6
(4.4…5.3)
VAC LOAD
OPL-4
OPL-3
OPL-2
OPL-1
2094-BL02
(460V)
VAC LINE
IPL-4
IPL-3
IPL-2
IPL-1
4.0
(12)
10.0
(0.38)
1.5…1.8
(13.2…15.9)
VAC LOAD
OPL-1
OPL-2
OPL-3
OPL-4
Common
(230V or 460V)
Control power output
CPL-2
CPL-1
L1
L2/N
2.5
(14)
10.0
(0.38)
0.5…0.6
(4.4…5.3)
Brake and I/O power
output
PSL-1
PSL-2
PSL-3
PSL-4
MBRK PWR
MBRK COM
MBRK PWR
MBRK COM
L3
L2
L1
L3’
L2’
L1’
L3
L2
L1
L3’
L2’
L1’
ATTENTION:
To avoid hazard of electrical shock, complete the wiring of your module
before applying power. Once power is applied, connector terminals may have voltage
present even when not in use.
ATTENTION:
The input power for Bulletin 2094 line interface modules must come from
a grounded configuration. When an ungrounded power configuration is used, phases
L1, L2, and L3 (without a reference to earth ground) can drift and stress the line-filter
components internal to the line interface module.
ATTENTION:
Your Bulletin 2093, 2094, and 2099 servo drive user manual includes
examples of grounded and ungrounded power configurations. See
Additional
Resources
on
page 56
for publication numbers.
Summary of Contents for 2094-AL09
Page 57: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 Line Interface Module 57 Notes...
Page 58: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 58 Line Interface Module Notes...
Page 59: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 Line Interface Module 59 Notes...