Contactor Coil
For safety reasons, the internal wiring is arranged so that if the control power
(CPL) circuit breaker (CB2) trips, the opening contact will interrupt the coil
voltage and remove main input power to the drive.
The 2094-AL
xx
S, 2094-BL
xx
S, and 2094-XL75S-C
x
line interface modules use
an AC coil and a DC interface module allows the contactor coil to be controlled
by the 24V DC output of the drive. Additional surge suppression is not required
for these contactors.
Figure 13 - IOL Contactor Coil
(catalog numbers 2094-AL
xx
S, 2094-BL
xx
S, and 2094-XL75S-C
x
)
The contactors in the 2094-AL09 and 2094-BL02 line interface modules use a
DC coil. The contactor coil voltage is 24V DC with a suitably-rated surge
suppressor fitted inside the line interface module.
Figure 14 - IOL Contactor Coil
(catalog numbers 2094-AL09 and 2094-BL02)
IMPORTANT
ATTENTION:
Do not apply AC voltage to COIL_E1 and COIL_E2.
1
3
2
4
FB1
CB2_AUX
1
2
A1
A2
COIL_E1
IOL-7
CR1
Line Interface Module
DC Interface Module
E2
E1
A1
CB2
2
4
1
3
COIL_E2
IOL-8
CB2_AUX
COIL_A1
IOL-13
A1
A2
D1
COIL_A2
IOL-4
CR1
Line Interface Module
4
6
3
5
2
1
CB2
Summary of Contents for 2094-AL09
Page 57: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 Line Interface Module 57 Notes...
Page 58: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 58 Line Interface Module Notes...
Page 59: ...Rockwell Automation Publication 2094 IN005H EN P October 2012 Line Interface Module 59 Notes...