Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
Line Interface Module
31
Wire the Line Interface Module
This section provides wiring requirements for each connector on the line
interface module.
Wire should be copper with 75
°
C (167
°
F) minimum rating. Phasing of main
AC power is arbitrary and earth-ground connection is required for safe and
proper operation.
Use these tables to determine the recommended wire size, strip length, and
torque value for wiring your line interface module.
Figure 27 - Wiring Requirements
(catalog numbers 2094-AL
xx
S, 2094-BL
xx
S, and 2094-XL75S-C2)
IMPORTANT
The National Electrical Code and local electrical codes take precedence over the values
and methods provided.
Description
Connects to Terminals
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
VAC LINE
IPL-1
IPL-2
IPL-3
IPL-4
2.5…25
(14…4)
16.0
(0.63)
2.7
(24)
VAC LOAD
OPL-1
OPL-2
OPL-3
OPL-4
Auxiliary power input
(1)
APL-1
L2/N
0.2…4.0
(24…10)
7.0
(0.28)
0.5…0.6
(4.4…5.3)
APL-2
L1
Control power output
CPL-1
CTRL 1
0.2…4.0
(24…10)
7.0
(0.28)
0.5…0.6
(4.4…5.3)
CPL-2
CTRL 2
Auxiliary power output
P2L-1
P2L-2
P2L-3
P2L-4
AUX1_L1
AUX1_L2
AUX2_L1
AUX2_L2
0.2…4.0
(24…10)
7.0
(0.28)
0.5…0.6
(4.4…5.3)
Brake and I/O power output
P1L-1
P1L-2
P1L-3
P1L-4
P1L-5
P1L-6
IO_PWR2
IO_COM2
IO_PWR2
IO_COM2
IO_PWR2
IO_COM2
0.08…1.5
(28…16)
7.0
(0.28)
0.22…0.25
(1.9…2.2)
Status I/O
(21-pin terminal block)
IOL-1…IOL-21
0.5…1.5
(22…14)
6.0
(0.25)
1.13
(10)
(1) The auxiliary power input (APL) connector is present only on the 2094-XL75S-C
x
line interface modules.
L3
L2
L1
L3’
L2’
L1’