64
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 3
Start Using the Controller
Use Logix Designer to Change the Operation Mode
Dependent on the mode of the controller you specify by using the mode switch,
you can change the Operation mode of the controller in the Logix Designer
application.
After you are online with the controller and the controller mode switch is set to
Remote (REM or the center position), you can use the Controller Status menu in
the upper-left corner of the application window to specify these operation
modes:
•
Remote Program
•
Remote Run
•
Remote Test
REM
Remote Run
mode
—This mode is identical to
Run mode except you can edit the project online.
You are able to modify a project file online in
Remote Run mode.
Be sure to control outputs with care to avoid
injury to personnel and damage to equipment.
Remote Program
mode
—This mode is identical
to Program mode.
Remote Test
mode
—The controller mode during
which code is executing. I/O is not controlled, and
limited editing operations are available.
Output modules are commanded to their Program
mode state (on, off, or hold).
Outputs are commanded to their Program
mode state, which can cause a dangerous
situation.
Note:
The mode of the controller can be changed
from within the Logix Designer application.
PROG
Program mode
—The controller mode during
which programming language is not executing. I/O
is not controlled, and limited editing operations are
available.
Output modules are commanded to their Program
mode state (On, Off, or Hold).
In this position, controller modes cannot be
changed through the Logix Designer application.
Do not use Program mode as an emergency
stop (E-stop). Program mode is not a safety
device.
Outputs are commanded to their Program
mode state, which can cause a dangerous
situation.
Mode Switch
Position
Available Controller Modes
ATTENTION:
Summary of Contents for 1756-L63XT
Page 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Page 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Page 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Page 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Page 211: ......