Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
141
I/O Modules
Chapter 8
•
If the module has a Real Time Sample (RTS), disable it or set it to a rate
that is greater than the RPI.
•
You can add I/O modules until you reach these limits:
–
80% of CPU utilization of the 1756-CN2, 1756-CN2R, or
1756-CN2RXT communication module.
–
Less than 400,000 unscheduled bytes per second are displayed in
RSNetWorx for ControlNet software after the network has been
scheduled.
Online Additions—EtherNet/IP Considerations
When you add I/O modules to the EtherNet/IP network, make these
considerations:
•
The EtherNet/IP I/O modules that you add can be added as these
connection types:
–
Rack-optimized connections, including new and existing connections
–
Direct connections
•
You can add I/O modules until you reach the limits of the communication
connections of the module.
For EtherNet/IP module limitations, see the EtherNet/IP Modules in
Logix5000 Control Systems User Manual, publication
Determine When Data is
Updated
ControlLogix controllers update date asynchronously with the execution of logic.
Use this flowchart to determine when a producer, such as a controller, input
module, or bridge, sends data.