72
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 3
Start Using the Controller
Estimate the ESM Support
of the WallClockTime
The ESM provides support for the maintenance of the WallClockTime of the
controller when power is not applied. Use this table to estimate the hold-up time
of the ESM based on the temperature of the controller and installed ESM.
To check the status of the ESM, see
General Status Messages on page 186
.
Maintain the Battery (Only
1756-L6
x
Controllers)
This section explains how to monitor and maintain the lithium batteries that the
ControlLogix controllers support.
For further information, see the
Check the Battery Status
When the battery is approximately 95% discharged, these low-battery warnings
are indicated:
•
The BAT is solid red.
•
A minor fault (type 10, code 10) is logged.
Hold-up Time (in days)
Temperature
1756-ESMCAP
1756-ESMNRM
1756-ESMNSE
20
°
C (68
°
F)
12
12
0
40 °C (104
°
F)
10
10
0
60
°
C (140
°
F)
7
7
0
IMPORTANT
Any action that causes the 1756-L7
x
controller to reset (hard or soft), without
an ESM installed, results in the controller’s wal clock time of the controller
being reset to the factory default of 01/01/1998.
Table 6 - 1756-L6
x
Controllers and Compatible Batteries
Cat. No.
Series
Compatible Battery
1756-L61
1756-L62
1756-L63
A
1756-BA1
or
1756-BATA
or
1756-BATM
1756-L61
1756-L62
1756-L63
1756-L64
1756-L65
B
1756-BA2
1756-L63XT
B
Summary of Contents for 1756-L63XT
Page 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Page 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Page 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Page 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Page 211: ......