74
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 3
Start Using the Controller
1756-BATM Battery Module and Battery Life
Use the 1756-BATM battery module with any 1756-L6
x
/A controller. The
battery module is highly recommended for higher-memory controllers.
When the 1756-BATA battery within the 1756-BATM module is approximately
50% discharged, these low-battery warnings are indicated:
•
The BAT is solid red.
•
A minor fault (type 10, code 10) is logged.
Table 7 - Worst-case Estimates of 1756-BA1 Battery Life
Temperature
Battery Life Before BAT Status Indicator Turns On
Battery Life After BAT Status
Indicator Turns On and Power is Off
Power Off 100% Power Off 50%
Yearly Decrease
60 °C (140 °F)
22 days
43 days
23%
6 hrs
25 °C (77 °F)
21 days
42 days
17%
28 hrs
0 °C (32 °F)
14 days
28 days
17%
2.5 days
Table 8 - Worst-case Estimates of 1756-BATA Battery Life
Temperature
Battery Life Before BAT Status Indicator Turns On
Battery Life After BAT Status
Indicator Turns On and Power is Off
Power Off 100% Power Off 50%
Yearly
Decrease
60 °C (140 °F)
98 days
204 days
11%
104 days
25 °C (77 °F)
146 days
268 days
5%
157 days
0 °C (32 °F)
105 days
222 days
6%
113 days
IMPORTANT
If your project is not stored in nonvolatile memory, the use of the battery
module is highly recommended.
Summary of Contents for 1756-L63XT
Page 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Page 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Page 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Page 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Page 211: ......