56
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 3
Start Using the Controller
9.
Click OK.
10.
Close ControlFLASH software.
Use AutoFlash to Upgrade Firmware
To upgrade your controller firmware with the AutoFlash feature, complete these
steps.
1.
Verify that the network connection is made and your network driver is
configured in RSLinx software.
2.
Use the Logix Designer application to create a controller project at the
version you need.
3.
Click RSWho to specify the controller path.
IMPORTANT
If the SD card is locked and the Load Image option of the stored project is set to
On Power Up, the controller firmware is not updated as a result of these steps.
The previously stored firmware and project are loaded instead.