OG-X-FR openGear Frame v1.0r1 30 www.aja.com
1. Alarm Mute Button
The Alarm Mute button on the card-edge of the MFC-8322-S mutes the audio
alarm for two minutes. If a fault condition is still present when the mute time-out
ends, the card re-activates the audio alarm.
2. Alarm Config Jumper
The Alarm Config jumper enables or disables the audio alarm signal. The ALARM
LED is still lit if alarm conditions are occurring, but the audio will be off. Refer to
Figure 9
and the card labeling for jumper positions.
Figure 9. Alarm Config Jumper — Pin Positions
• Enabled — To enable the alarm feature, set the jumper into Position 1+2.
• Disabled — To disable the alarm feature, set the jumper into Position 2+3.
3. DIP Switches
SW1 and SW2 are used in conjunction with the DashBoard menus to set the IP
Address of the MFC-8322-S.
SW3 is used to override the Master Password for the MFC-8322-S. This password
limits access to the card, and the cards installed in the frame.
4. Card Lock
This lock located near the front edge of the card is used to secure the card in its
frame slot.
Configuring the DIP Switches
Figure 10. DIP Switches — Set to the ON Positions
SW1, SW2 — IP Address Setup
SW1 and SW2 are used in conjunction with the DashBoard menus to set the IP
Address of the MFC-8322-S (see
Table 2
).
Table 2. SW1 and SW2 Positions
SW1
Position
SW2
Position
Controlled via
DashBoard
Descriptions
OFF
OFF
YES
The card network settings can be
set by the user from the DashBoard
Network tab. (default). DHCP Mode
is assumed until the user changes
the settings in DashBoard.