11—CONTROL SYSTEM
11.5.2.4 Outdoor Unit NLOAD calculation
Compressor speed will be set between the minimum speed and the max speed according to
the ODU NLOAD
11.5.2.5 Speed Step Limitations
11.5.2.5.1 Step 1 and step 2
The compressor speed cannot go below Step1Freq or above Step2Freq during 3 continuous
minutes once after the compressor starts up when the ODU unit changes from STBY
11.5.2.5.2 Step 3 limit
The speed cannot go higher than Step3Freq unless it was operating for more than 1 continuous
minute between Step3Freq – 5 and Step3Freq.