11—CONTROL SYSTEM
SM YAZE218 1-A.2 GB | 11—15
11.5.7 Thermodynamic Protections
Protection level de nition
Five protection levels are de ned:
Normal – No protection status is ON.
Stop-Rise (SR) – System is in protection, rst level
D1 - System is in protection, second level
D2 - System is in protection third level
Stop-Compressor (SC) – System is in protection fourth level
11.5.8 IDU Protection Level
The overall protection level of the indoor units will be the worst protection status among the all
indoor units.
11.5.9 IDU Protections
11.5.9.1 Indoor Coil Defrost Protection
ICT
ICT Trend
Fast
Increasing
Increasing
No change
Decreasing
Fast Decrea-
sing
ICT < -2
SC
SC
SC
SC
SC
-2
≤
ICT < 0
D1
D1
D2
D2
D2
0
≤
ICT < 2
SR
SR
D1
D2
D2
2
≤
ICT < 4
SR
SR
SR
D1
D2
4
≤
ICT < 6
Norm
Norm
SR
SR
D1
6
≤
ICT < 8
Norm
Norm
Norm
SR
SR
8
≤
l
a
m
r
o
N
T
C
I
11.5.9.2 Indoor Coil over Heating Protection
ICT
ICT Trend
Fast
Decreasing Decreasing No Change Increasing
Fast
Increasing
ICT > 55
SC
SC
SC
SC
SC
53 < ICT
≤
55
D1
D1
D2
D2
D2
49 < ICT
≤
53
SR
SR
D1
D2
D2
47 < ICT
≤
49
SR
SR
SR
D1
D2
45 < ICT
≤
47
Norm
Norm
SR
SR
D1
43 < ICT
≤
45
Norm
Norm
Norm
SR
SR
ICT
≤
l
a
m
r
o
N
3
4
Summary of Contents for YAZE218
Page 11: ...4 1 SM YAZE218 1 A 2 GB 4 OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 Indoor Unit HJD009 012 ...
Page 25: ...6 2 SM YAZE218 1 A 2 GB 6 OPERATING CURVES 6 1 2 Heating Technician Mode ...
Page 26: ...SM YAZE218 1 A 2 GB 6 3 6 OPERATING CURVES 6 1 3 Tubing Length correction Factor ...
Page 28: ...SM YAZE218 1 A 2 GB 8 1 8 WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 YAZE218 Wiring Diagrams ...
Page 29: ...8 WIRING DIAGRAMS 9 1 SM YAZE218 1 A 2 GB 9 REFRIGERATION DIAGRAMS 9 1 YAZE218 Cooling Mode ...
Page 30: ...8 WIRING DIAGRAMS SM YAZE218 1 A 2 GB 9 2 9 2 YAZE218 Heating Mode ...
Page 77: ...14 1 SM YAZE218 1 A 2 GB 14 APPENDIX A 14 APPENDIX A INSTALLATION AND OPERATION MANUAL ...
Page 78: ...SERVICE MANUAL YAZE218 ...