12—TROUBLESHOOTING
SM YAZE218 1-A.2 GB | 12—2
No
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
- Repair if needed
PFC Chock coil
Check the PFC Chock coil
Burnt fuse
Check 20A fuse on the Filter (12.4.2)
10.
Compressor operates but one or more
units generates no capacity
EEV problem
Check EEV (12.4.5)
Refrigerant leakage
Check refrigeration system (12.2)
Indoor coil block
Clean lters and/or remove block
Outdoor coil block
Remove block and/or avoid air
by-pass
11.
Compressor is over heated and unit
does not generate capacity
EEV problem
Check EEV (12.4.5)
Refrigerant leakage
Check refrigeration system (12.2)
Indoor coil block
Clean lters and/or remove block
Outdoor coil block
Remove block and/or avoid air
by-pass
12.
Compressor stops during operation
Electronic control
Check diagnostics (see 12.3 below)
Refrigerant leakage
Check refrigeration system (12.2)
13.
Not all units are operating
Communication problems
Check diagnostics (see 12.3 below)
14.
Compressor does not start
Electronics control problem or
protection
15.
Unit works in wrong mode (cool instead of
heat or heat instead of cool)
Electronics or RV problem
Check RV (12.4.4)
16.
All components are operating properly
but no cooling or no heating
Refrigerant leak
Check refrigeration system (12.2)
17.
Compressor motor is generating noise
and no suction occurs
Phase order to compressor
is wrong
Check compressor phase order
18.
Freezing of outdoor unit in heat mode
and outdoor unit base is blocked with ice
Connect base heater
19.
The unit stop suddenly during operation
EMC interference to the A/C
unit
Check for EMC problems
(12.4.8.1)
20.
Indoor unit(s) Indicator(s) leds may icker
21.
Other home appliances operation is faulty
such as noise appears in the television
picture, or the picture is distorted or static
occurs in the radio sound
EMC interference by the A/C
unit
Check for EMC problems
(12.4.8.2)
22.
All others
Speci c problems of indoor
or outdoor units
Check diagnostics (see 12.3
below)
12.2
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system is in
technician Mode where the system operates as in xed settings. The performance curves given in this
manual are given for unit performance in Technician mode when high indoor fan speed is selected. For
entering technician mode, refer to 11.7.
Summary of Contents for YAZE218
Page 11: ...4 1 SM YAZE218 1 A 2 GB 4 OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 Indoor Unit HJD009 012 ...
Page 25: ...6 2 SM YAZE218 1 A 2 GB 6 OPERATING CURVES 6 1 2 Heating Technician Mode ...
Page 26: ...SM YAZE218 1 A 2 GB 6 3 6 OPERATING CURVES 6 1 3 Tubing Length correction Factor ...
Page 28: ...SM YAZE218 1 A 2 GB 8 1 8 WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 YAZE218 Wiring Diagrams ...
Page 29: ...8 WIRING DIAGRAMS 9 1 SM YAZE218 1 A 2 GB 9 REFRIGERATION DIAGRAMS 9 1 YAZE218 Cooling Mode ...
Page 30: ...8 WIRING DIAGRAMS SM YAZE218 1 A 2 GB 9 2 9 2 YAZE218 Heating Mode ...
Page 77: ...14 1 SM YAZE218 1 A 2 GB 14 APPENDIX A 14 APPENDIX A INSTALLATION AND OPERATION MANUAL ...
Page 78: ...SERVICE MANUAL YAZE218 ...