11—4 | SM YAZE218 1-A.2 GB
11—CONTROL SYSTEM
11.3.2.2 ‘Bad Communication’ fault
The system keeps a balance of a good/bad communication packet ratio for each active
communication channel. When the ratio getting high , system enters ‘Bad Communication’ fault.
11.3.2.3 ‘No Communication’ fault
If no legal transmission or no message received for 30 seconds, system enters ‘No
Communication’ fault.
When in ‘No Communication’ fault, the system will act as following:
●
If there is no communication in all channels, the following will be performed:
1. The unit changes to SB.
2. The system will scan all the communication.
3. Each channel that is identi ed as ‘no communication’ channel will be referred as
STBY unit.
4. The unit resumes its normal operation with only the operative channels.
11.3.3 Temperature Measurements
11.3.3.1 Thermistor failures de nition
Thermistor
Type a – Disconnected
Type b – Shorted
OAT
Temp < -30°C
Temp > 75°C
OCT
Temp < -35°C
Temp > 75°C
CTT
Temp < -30°C
Temp > 125°C
HST
Temp < -30°C
Temp > 125°C
OMT
Temp < -35°C
Temp > 75°C
ICT
Temp < -30°C
Temp > 75°C
RGT
Temp < -30°C
Temp > 126°C
RLT
Temp < -30°C
Temp > 126°C
11.3.3.2 System responses for different thermistor failure
Thermistor
Default value
System Reaction
OCT
43°C
OAT
6°C
CTT
43°C
Compressor is stopped.
OMT
43°C
Compressor is stopped in cooling mode.
HST
43°C
Compressor is stopped.
RGT
43°C
RLT
43°C
ICT
43°C
11.3.4 Flash Memory Programming
In order to upgrade the ODU software the auxiliary port will be used. A special application
should be run on a PC to transmit the new rmware. Special programmer (Panasonic) should
be used to update the S/W.
Summary of Contents for YAZE218
Page 11: ...4 1 SM YAZE218 1 A 2 GB 4 OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 Indoor Unit HJD009 012 ...
Page 25: ...6 2 SM YAZE218 1 A 2 GB 6 OPERATING CURVES 6 1 2 Heating Technician Mode ...
Page 26: ...SM YAZE218 1 A 2 GB 6 3 6 OPERATING CURVES 6 1 3 Tubing Length correction Factor ...
Page 28: ...SM YAZE218 1 A 2 GB 8 1 8 WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 YAZE218 Wiring Diagrams ...
Page 29: ...8 WIRING DIAGRAMS 9 1 SM YAZE218 1 A 2 GB 9 REFRIGERATION DIAGRAMS 9 1 YAZE218 Cooling Mode ...
Page 30: ...8 WIRING DIAGRAMS SM YAZE218 1 A 2 GB 9 2 9 2 YAZE218 Heating Mode ...
Page 77: ...14 1 SM YAZE218 1 A 2 GB 14 APPENDIX A 14 APPENDIX A INSTALLATION AND OPERATION MANUAL ...
Page 78: ...SERVICE MANUAL YAZE218 ...