11—24 | SM YAZE218 1-A.2 GB
11—CONTROL SYSTEM
11.7
Technician Test Mode
This test is aimed for the technicians to check the system under a preset compressor and outdoor fan
values while the expansion valves will function according to the normal running mode.
11.7.1 Entering technician mode
o
This mode is entered through the outdoor unit using the HMI (refer to user
interface section).
o
It can be selected either for cool or heat.
o
Technician test is not possible to enter during deicer.
11.7.2 Technician mode procedure
●
All the connected indoor units will enter technician test at high indoor fan speed.
●
The outdoor unit will be working normally (according to the run mode control
logic) except the following changes:
o
The dry contacts inputs will be ignored.
o
Protections will be operative for stop compressor (not to be implemented in the
current version).
o
The compressor and the outdoor fan will be working in target preset values
according to the following table:
Technician Test
Unit
Compressor Speed
OFAN speed
Cool
Heat
m
p
r
0
0
9
8
8
6
6
8
1
2
Z
A
Y
11.7.3 Exiting technician mode
Technician mode will be exited either when:
o
Escaping by the HMI (exiting the ttC or ttH menus)
o
60 minutes are passed from entering
Summary of Contents for YAZE218
Page 11: ...4 1 SM YAZE218 1 A 2 GB 4 OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 Indoor Unit HJD009 012 ...
Page 25: ...6 2 SM YAZE218 1 A 2 GB 6 OPERATING CURVES 6 1 2 Heating Technician Mode ...
Page 26: ...SM YAZE218 1 A 2 GB 6 3 6 OPERATING CURVES 6 1 3 Tubing Length correction Factor ...
Page 28: ...SM YAZE218 1 A 2 GB 8 1 8 WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 YAZE218 Wiring Diagrams ...
Page 29: ...8 WIRING DIAGRAMS 9 1 SM YAZE218 1 A 2 GB 9 REFRIGERATION DIAGRAMS 9 1 YAZE218 Cooling Mode ...
Page 30: ...8 WIRING DIAGRAMS SM YAZE218 1 A 2 GB 9 2 9 2 YAZE218 Heating Mode ...
Page 77: ...14 1 SM YAZE218 1 A 2 GB 14 APPENDIX A 14 APPENDIX A INSTALLATION AND OPERATION MANUAL ...
Page 78: ...SERVICE MANUAL YAZE218 ...