11.4.3.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
11.4.4 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (
∆
T).
Unit will switch from cool to heat when compressor is off for 3 minutes, and
∆
T < -3. Unit will
switch from heat to cool when compressor is off for 5 minutes, and
∆
T < -3.
11.4.5 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.4.6 Indoor Units Operation when Indoor Unit Mode is Different than
Outdoor Unit Mode
●
Open louvers according to user selection.
●
Indoor fan is forced to OFF.
11.4.7 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J9.
Status
Function
Contact = Open
Contact = Short
J9 = Open
Presence Detector Connection
No Limit
Forced to STBY
J9 = Short
Power Shedding Function
No Limit
Limit NLOAD
11.4.8 Operating the Unit from the Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature
according to the following table:
Forced operation Mode
Pre-set Temperature
C
0
0
2
g
n
il
o
o
C
C
0
8
2
g
n
it
a
e
H
Summary of Contents for YAZE218
Page 11: ...4 1 SM YAZE218 1 A 2 GB 4 OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 Indoor Unit HJD009 012 ...
Page 25: ...6 2 SM YAZE218 1 A 2 GB 6 OPERATING CURVES 6 1 2 Heating Technician Mode ...
Page 26: ...SM YAZE218 1 A 2 GB 6 3 6 OPERATING CURVES 6 1 3 Tubing Length correction Factor ...
Page 28: ...SM YAZE218 1 A 2 GB 8 1 8 WIRING DIAGRAMS 8 WIRING DIAGRAMS 8 1 YAZE218 Wiring Diagrams ...
Page 29: ...8 WIRING DIAGRAMS 9 1 SM YAZE218 1 A 2 GB 9 REFRIGERATION DIAGRAMS 9 1 YAZE218 Cooling Mode ...
Page 30: ...8 WIRING DIAGRAMS SM YAZE218 1 A 2 GB 9 2 9 2 YAZE218 Heating Mode ...
Page 77: ...14 1 SM YAZE218 1 A 2 GB 14 APPENDIX A 14 APPENDIX A INSTALLATION AND OPERATION MANUAL ...
Page 78: ...SERVICE MANUAL YAZE218 ...