6
3.2.4. DAY/NIGHt INPUt DI10
this input is used with the domestic hot water option only when the parameter l01 is set as "in". When the contact
is in night mode then the "comfort" setpoint (parameter o02) is used when the contact is in day mode the "eco"
setpoint (parameter o03) is used.
this input can be used with an off peak electricity meter.
the parameter l08 can be used to inverse the input.
²
if l08 = dir (default setting) then when the input is closed the night mode is on.
²
if l08 = inv then when the input is closed the daytime "eco" setpoint is used.