6.3.1.2. DAILY SCHEDULING
tHIS FUNCtIoN REqUIRES tHE tIME to BE SEt.
two start and stop times can be programmed per day. all days are the same.
it is not necessary to use both timers. the default setting is timer 2 set to 0.
the default values are:
²
o04
timer 1 start
23h
²
o05
timer 1 stop
03h
²
o06
timer 2 start
00h
²
o07
timer 2 stop
00h
in the above case the "comfort" setpoint will be used from 23h00 in the evening to 03h00 in the morning and
the "eco" setpoint will be used the from 03h00 in the morning to 23h00 in the evening. the timer 2 settings are
not used.
the timer settings are changed in hours. it is not possible to use minutes.
6.3.1.3. EXAMPLES oF DIFFERENt DHW oPERAtING PAttERNS
Heating and DHW mode operation in relation to scheduling,
restart after night time running
these examples are provided for information purposes only. the different heating
or DHW production timeframes are not necessarily representative of all possible
installations. these heating times are closely linked to the Aqu@ Scop Advance DCI’s
operating conditions, to the type of heat exchangers and the level and frequency of
demand for DHW.
0
1
HEATING / DHW MODE
Heating
mode
DHW Mode
TIME OF DAY
04:30
05:00
05:30
06:00
06:30
07:00
07:30
08:00
08:30
09:00
09:30
10:00
10:30
11:00
11:30
12:00
HEATING
MODE
HEATING
MODE
DHW
MODE
DHW
MODE
15
16
17
18
19
20
21
22
ROOM TEMPERATURE (°C)
Room SPT
Room T.
30
35
40
45
50
55
DHW TEMPERATURE (°C)
DHW SPT
DHW T.
DHW > Eco se 2°C
End of DHW
Room T. > 18°C for a
setpoint at 20°C
DHW production
DHW demand but roomT.
< 18°C for a setpoint at
20°C