12
6.2.2. DHW MANAGEMENt RELAtIVE to RooM tEMPERAtURE
When the room terminal is connected, the
Aqu@ Scop Advance DCI
can decide whether to give priority to
heating or dhW production.
the dhW or heating priority can be configured by the parameter l02:
²
if the room temperature is lower than the room setpoint minus 2°c, the
Aqu@ Scop Advance DCI
remains in heating mode until the room temperature returns above this limit. For example, for a
room setpoint of 20°c, the switchover to dhW will only occur if the room temperature is above 18°c
(during 5 consecutive minutes).
²
beyond a certain time of demand for dhW production, the
Aqu@ Scop Advance DCI
will
automatically switch to dhW mode, irrespective of the room temperature. this time period, l02 set
at 60 minutes, is a good compromise between heating comfort and readily available domestic hot
water. Moreover, if the timer has been programmed or if an off-peak hours electricity relay has been
connected to the
Aqu@ Scop Advance DCI
, this set-up ensures that the optimum time period for
dhW production is not missed.
to afford greater priority to heating for example, the l02 value can just be increased (up to 4 hours). in this case,
the
Aqu@ Scop Advance DCI
will be able to remain in heating mode for 4 hours or until the room temperature
has reached the room setpoint. however, there is a risk of not having dhW at the desired temperature at the end
of the off-peak period, for example.
on the other hand, priority can be given to dhW by changing the l02 value to 0 minute.
VALUE
L08
VALUE
L07
VALUE
L06
VALUE
L05
VALUE
L04
VALUE
L03
VALUE
L02
VALUE
L01
+
Exits without changing the value
Stores the new value
Decreases the value
Increases the value
+
+
DHU
+
0
+
PSS
+
LWT / OFF
6.2.3. AqU@ SCoP ADVANCE DCI IN HEAtING oFF MoDE
When the
Aqu@ Scop Advance DCI
is in off mode (refer to the §
oN/oFF
, page 5), the room temperature
is no longer taken into account and the changeover to dhW mode is instantaneous during a demand for dhW
production.
6.2.3.1. RooM tERMINAL Not CoNNECtED
When the room terminal is not connected to the
Aqu@ Scop Advance DCI
, the changeover to dhW mode is
identical to operation in off mode.
6.3. CoMFoRt/ECo tEMPERAtURE SEtPoINtS (SCHEDULING)
the user can set the dhW parameters to fulfil all types of needs. to achieve this, the
Aqu@ Scop Advance DCI
proposes two temperature setpoints: comfort and eco, as well as two operating modes: Permanent comfort and
comfort/economy. similarly, there are two types of timer programming: via digital input (dry contact) or via daily
scheduling (timer programming).
VALUE
o13
VALUE
o12
VALUE
o11
VALUE
o10
VALUE
o09
VALUE
o08
VALUE
o07
VALUE
o06
VALUE
o05
VALUE
o04
VALUE
o03
VALUE
o02
VALUE
o01
Increases the value
Decreases the value
Stores the new value
+
Exits without changing the value
+
ECS
+
PAr
+
LWT / OFF
o01
: comfort permanent selection
o02
: comfort setpoint (default=48°c)
o03
: eco setpoint (default=45°c)