38
PARAMEtRE
UNIt
MIN
MAX
DEFAULt
tYPE
Par / ecs
o01
Permanent comf. mode
on = permanent comfort mode
off = dry contact or programmed
mode
on
modifiable
o02
comfort period setpoint
°c
10
60
48
modifiable
o03
eco period setpoint
°c
10
55
45
modifiable
o04
start time for comfort period 1
hr
0
23
23:00
modifiable
o05
stop time 1
hr
0
23
03:00
modifiable
o06
start time for comfort period 2
hr
0
23
0
modifiable
o07
stop time 2
hr
0
23
0
modifiable
o08
anti-legionellosis function on/oFF
on
off
off
modifiable
o09
Water setpoint in anti-legionellosis mode
°c
0
70
60
modifiable
o10
day of anti-legionellosis cycle
day
1 (Monday)
7
1
modifiable
o11
start time of anti-legionellosis cycle
hr
0
23
01:00
modifiable
o12
duration of anti-legionellosis cycle
min
0
90
30
modifiable
o13
manual rapid charge
on = hot water tank heated by compressor and
resistance
off = normal
modifiable
Pss /
cnF
h08
activation of hot Water
on = dhW activated
off = no dhW
oFF
modifiable
h09
selection of heat curve
0 = radiator
1 = underfloor
2 = fixed (no heat curve))
1
modifiable
h10
selection of unit
0 = electric heater
1 = boiler back-up
2 = no additional heating
modifiable
h11
activation of outside air temperature
sensor
oFF = use inside sensor
on = use a wall-mounted air
temperature sensor
oFF
modifiable
h12
activation of ambience remote control
on = room terminal activated
(recommended)
oFF = no room terminal
on
modifiable
h14
heat curve outside air temperature
setpoint
°c
0
25
15°c
modifiable
h15
heat curve outside air delta temperature
setpoint
°c
0
40
15 °c
underfloor
25 °c
radiator
modifiable
h16
heat curve Max compensation of water
temperature
°c
0
20
10°
underfloor
12°
radiator
modifiable
h19
electric heater differential
°c
0
6
3
modifiable
h20
electric heater hysteresis
°c
0
3
1
modifiable
h21
outside air temperature for shut-down of
eh1 or boiler
°c
5
modifiable
h22
outside air temperature for shut-down
of eh2
°c
2
modifiable
h23
outside air temperature for shut-down
of compressor
°c
-20
20
-5°c
(back-up)
20°c
(resistance)
modifiable
h24
reversal of boiler bypass outlet direction
0 = the bypass valve is energised
when the boiler is off.
1 = the bypass valve is energised
when the boiler is on
0
modifiable
h25
reversal of "eJP" tariff intake logic
dir = input closed = "eJP" tariff
mode on
inv = input open = "eJP" tariff
mode on
0
modifiable