PARAMEtRE
UNIt
MIN
MAX
DEFAULt
tYPE
Pss /
cnF
h26
supply voltage used for kWh estimation
V
200
250
225
modifiable
h27
D
t for compressor restart
°c
0.2°c
modifiable
h28
D
t for compressor shut-down
°c
0.6°c
modifiable
h29
input 9 selection on / off or electric heat
load shedding
oF = on / off
ls = electric heat load shedding
oF
modifiable
h30
reverse input 9 (on/off or load shedding)
dir = input closed = on
inv = input open = on
inv
modifiable
h31
Maximum possible water temperature for
floor heating
°c
30
55
45
modifiable
Pss / PuP
P01
type of water pump operation
0 = continuous operation even
when in off mode.
1 = continuous operation except
when in off mode.
2 = operation on demand from
compressor
2
modifiable
P02
interval between anti-seize cycles
hours
0
99
24
modifiable
P03
length of anti-seize cycle
s
0
999
60
modifiable
P04
configuration of water pump WP2
0 = used with a mixing tank. on /
off as a function of
D
t below.
1 = operation as boiler back-up.
on with bypass valve.
0
modifiable
P05
restart water pump WP2
°c
-2.0
2.0
0.2
modifiable
P06
shut-down of water pump WP2
°c
-2.0
2.0
0.6
modifiable
Pss / dFr
d01
time remaining until defrost
min
read only
d02
corrected temperature at start of defrost
timer
°c
read only
d03
temperature at start of de-ice timer before
correction
°c
-2
read only
d04
interval between de-icing cycles
min
40
60
50
modifiable
d05
end of de-ice
°c
16
read only
Pss / rtc
hr
time used
hr / min
read only
dat
date used
dd / mm
/ yy
read only
chd
update the date
modifiable
chh
update the time
modifiable
Pss /
dhu
l01
selection of switch-over mode between
comfort and eco
Prg = uses hour programming
in = uses day / night inPut
Prg
modifiable
l02
dhW cycle start time if
D
t< 2
min
0
240
60
modifiable
l03
type of dhW kit
0 = dhW tank
1 = dhW
module with
pump
0
modifiable
l04
dhW module pump cycle time interval
min
10
300
120
modifiable
l05
use the internal elec heat for dhW
additional heat
on = internal elec heat
oFF = dhWeh used
oFF
modifiable
l06
compressor can be used for dhW for
boiler relief and low oat
on = compressor used
oFF = compresseur not used
oFF
modifiable
l07
comp and dhWeh used for boiler
back-up config only
on = dhW by comp and dhWeh
oFF = dhW by comp and boiler
oFF
modifiable
l08
reverse input 10 (day / night)
dir = input closed = night mode
inv = input open = night mode
dir
modifiable