19. PARAMEtERS
installer password is 177
the after sales service parameters are in the menu s02 to s18. these parameters can only be modified by airwell
personnel.
PARAMEtRE
UNIt
MIN
MAX
DEFAULt
tYPE
set
hea
initial setpoint for the heating law
°c
20 °c underfloor
or 30 °c
radiator
40°c underfloor
or 50°c radiator
27.5/38
modifiable
her
Water setpoint after correction
°c
read only
o-F
on oFF
on/ oFF
on
off
oFF
modifiable
ec
ecs comfort setpoint
°c
10
60
48
modifiable
tP
t01
Water inlet temperature b1
°c
-50°c
90 °c
read only
t02
Water outlet temperature b2
°c
-50°c
90 °c
read only
t03
outside coil temperature b3
°c
-50°c
90 °c
read only
t04
outside air temperature b4
°c
-50°c
90 °c
read only
t05
discharge temperature b5
°c
0
120 °c
read only
t06
sunction temperature b6
°c
-50°c
90 °c
read only
rt
ambience temperature
°c
0°c
40°c
read only
P07
sunction pressure b7
bar
0
15
read only
t08
hot water temperature b8
°c
-50°c
90°c
read only
i-0 /do
1 -
status of output no1
0 = output open
1 = output
energised
read only
2 -
status of output no2
0 = output open
1 = output
energised
read only
3
0 = output open
1 = output
energised
read only
et....12 …..status of output no12
0 = output open
1 = output
energised
read only
i-0 / dl
1 -
status of input id1
0 or 1
0 = output not
energised
1 = output
energised
read only
etc....10 ….. status of input id10
0 or 1
0 = output not
energised
1 = output
energised
read only
i-0 / eeV
pos
Position of expansion valve
pitch
0
480
read only
sh
superheating
K
0
40
read only
i-0 / dci
sPd
compressor speed
hz
0
80
read only
cur
current
a
0
30
read only
i-0
Fan
Fan speed
%
0
100
read only
th
thermostat setpoint
°c
0
30
read only
dFr
time until next defrost
minutes
0
60
read only
ele
estimated consumption in kWh.
kWh
0
999999
read only
i-o / ecs
sta
hot water status
"off" = dhW stopped
"on" = dhW operating
"leg" = anti-legionellosis operating
read only
Val
current value of hot water setpoint
°c
10
65
read only
err
alarms
code
read only
log
alarm log
code
read only
Par / cnF
h01
software version
read only
h03
type of water curVe
0 = radiator
1 = underfloor
2 = no heat curve
read only
h04
type of dci
Model 6, 12 or 16
read only
h05
sPh or dci
compressor configuration
0 = fixed
1 = variable
read only