3 DHW schedulings (via off-peak hours input or daily scheduling)
without consideration for Heating demand
off-peak input connected or default daily scheduling (comfort between 23h00 and 05h00 in the morning, eco
the rest of the time), comfort and eco setpoints at 50°c and 45°c.
40
42
44
46
48
50
52
54
56
58
60
DHW TEMPERATURE (°C)
TIME OF DAY
22 23 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 00 01
DHW SPT
DHW T.
DHW > Eco SPT - 2°C
No restart in Eco mode
DHW < Eco SPT - 2°C
Restart in Eco mode
DHW OFF at Comfort SPT + 2°C
Temp. exceeded due to system inertia.
off-peak input connected or daily scheduling with a restart at midday (comfort between 0h00 and 05h00 in the
morning and between 12h00 and 14h00, eco the rest of the time), comfort and eco setpoints at 50°c and 45°c.
40
42
44
46
48
50
52
54
56
58
60
TIME OF DAY
22 23 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 00 01
DHW SPT
DHW T.
DHW TEMPERATURE (°C)
DHW OFF at Comfort SPT + 2°C
Temp. exceeded due to system inertia.
DHW > Eco SPT - 2°C
No restart in Eco mode
DHW < Eco SPT - 2°C
Restart in Comfort mode