14. RooM tERMINAL
either the wired or the rF versions can be used. there is no difference in configuration for the heat pump.
the communication between the main controller and the room terminal or the transmitter is in rs485 Modbus.
the room temperature value measured by the room terminal can be seen at tP -> rt. the instantaneous setpoint
can be seen at i-o -> th.
the alarm e16 (no communication with room terminal) does not prevent the heat pump from working.
VALUE
TH
CONSULTATION
+
}
+
I-0
+
LWT / OFF
VALUE
RT
CONSULTATION
+
}
+
tP
+
LWT / OFF
14.1. ANtICIPAtIoN
the heatpump automatically starts early to anticipate mode change when changing from night mode (
) to
comfort mode (
) when automatic scheduling is being used. the algorithm presumes that the room temperature
can increase 4°c per hour then calculates the difference between room temperature and the comfort setpoint
and starts early in comfort mode. For example if there is a 2°c difference between room temperature and comfort
setpoint the comfort mode will start 30 minutes before the programmed time.