lnstallation and Maintenance
7. Electrical lnstallation
• Use an ELB (Electric Leakage Breaker). lf not used, it may cause an electric shock or a tire.
• Do not operate the system until all the check points have been cleared.
(A) Check to ensure that the insulation resistance is more than 2 MO, by measuring the resistance between
ground and the terminal of the electrical parts. lf not, do not operate the system until the electrical leakage
is found and repaired.
(B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start the system.
Model Capacity
Transmitting Cable Size
(X100W)
EN60335-1
26-175
4X1.5mm'
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked in the table are selected at the maximum current of the unit according to the
European Standard, EN60335-1. Use the wires which are not lighter than the ordinary polychloroprene
sheathed flexible cord (code designation H07RN-F).
When connecting the terminal block using flexible cord, make sure to use the round crimp-style terminal
for connection to the power supply terminal block.
Place the round crimp-style terminals on the wires up to the covered
part and secure in place.
Terminal
When connecting the terminal block using a single core
wire, be sure to perform curing.
(6) Single core wire
-n✓
111w.11r11r1
3) When transmitting cable length is more than 15 meters, a larger wire size should be selected.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
Flexible cord
5) In the case that power cables are connected in series, add each unit maximum current and select wires below.
Selection According to EN60335-1
Current i(A)
Wire Size(mm')
¡,,;5
o. 75
6<i,,;10
1
10<i,,;16
1.5
16<i,,;25
2.5
25<j,,;32
4
32<i,,;4o
6
40<¡,,;53
10
63<i
*
*In the case that current exceeds 63A, do not connect cables in series.
8. Trial Run
Please perform trial run according to outdoor unit installation manual.
55
Summary of Contents for ORIA 18 INT
Page 2: ...MANUAL DE USUARIO E INSTALACIÓN ESPAÑOL CASSETTE ORIA 18 INT ORIA 24 INT ORIA 36 INT ORIA ...
Page 3: ...2 ...
Page 4: ...3 ...
Page 5: ...4 5 12 13 13 13 14 15 17 17 18 18 23 24 26 27 27 ...
Page 29: ...28 ...
Page 30: ...OWNER S AND INSTALLATION MANUAL ENGLISH CASSETTE ORIA 18 INT ORIA 24 INT ORIA 36 INT ORIA ...
Page 32: ...31 ...
Page 33: ...32 33 40 41 41 41 42 43 45 45 46 46 46 52 54 55 55 ...
Page 57: ...56 ...
Page 58: ...PORTUGUÊS MANUAL DO UTILIZADOR E INSTALAÇÃO CASSETTE ORIA 18 INT ORIA 24 INT ORIA 36 INT ORIA ...
Page 59: ...58 ...
Page 60: ...59 ...
Page 61: ...60 61 68 69 69 69 70 71 73 73 74 74 74 80 82 83 83 ...
Page 85: ...84 ...
Page 86: ...ITALIANO MANUALE DI UTENTE E INSTALLAZIONE CASSETTE ORIA 18 INT ORIA 24 INT ORIA 36 INT ORIA ...
Page 87: ...86 ...
Page 88: ...87 ...
Page 89: ...88 89 96 97 97 97 98 99 101 101 102 102 102 108 110 111 111 ...
Page 90: ...89 ...