5.4.4 Maintenance of Battery
Battery may generate hydrogen gas and may explode. Therefore, recharging should be done at a
well-ventilated place.
Do not check the battery by short-circuiting the positive and negative terminals with a metallic
piece.
Never operate the machine nor charge the batteries with low battery liquid. Continuing operation
at this lower level will cause deterioration of some parts, reduction of battery life, and also it may
cause explosions. Add distilled water so that the liquid level is between the “UPPER LEVEL” and
“LOWER LEVEL” if the level is too low.
Wear protective gloves and safety glasses when handling a battery.
If battery electrolytes contact your clothes or skin, wash it away with a large amount of water
immediately.
If the battery electrolytes get into your eyes, flush them immediately with plenty of water and see
a doctor at once. Severe damage to eyes and vision may result.
D004
W010
TR0093
Handling Battery
K
eep flames away from battery.
Do not spark near the battery nor light a match, nor bring lit
cigarette and match close to the battery.
Do not charge a frozen battery as it may explode. If the battery is
frozen, warm it up until the battery temperature becomes 16°C to
30°C.
Battery electrolyte is diluted sulfuric acid. In case of mishandling,
it could cause skin burning.
Dispose of battery, observing local regulations.
[Charge battery]
Use the battery charger after you confirm whether it is in good operating condition and ready for
use.
Disconnect the cable between battery and the machine, and charge the battery with a 12V battery
charger. Do not charge two batteries at the same time.
Be sure not to connect (+) and (–) terminals backwards.