3. Operation
3-2
3.2 Simultaneous usage of three-phase and single-phase power
This generator is capable of simultaneously outputting three-phase and single-phase power with no
need to switch output settings.
[3
Φ
, 4 wire and 1
Φ
, 3 wire setup for simultaneous use]
3
Φ
Load 1
Φ
Load
A180745
Make sure that the combined three-phase and
single-phase output does not exceed the total
allowable current for the unit (see sample table
below).
※
Refer to section 3.3 for instructions on how to connect
three-phase or single-phase loads.
Output
Allowable current during
simultaneous use(A)
3
Φ
, 4 wire
(240V)
0 10 20 30
1
Φ
, 3 wire
(240V)
40 28 14 0
[Checking current during simultaneous use]
A160303E
Using the ammeter, check to make sure that each
phase is within limits. See table below for the
required current selector setting for each phase to be
tested.
Current Selector
Phases being measured
3
Φ
, 4 wire
1
Φ
, 3 wire
U L1
U1
V L2 -
W L3
W1
Go
to