2. Transportation and Installation
2-4
SG0103-1
The unit should be installed within 5
゚
degree
inclination.
If installation site is not flat, put square bar under the
unit so as to install it horizontally.
Avoid installing the unit in a damp place or a place
where water collects. Such an installation could cause
electric shock.
When installing the unit at the sea shore, make sure
that it is not exposed directly to sea water because
there is a risk of the change to the insulation
resistance of the generator assembly or control panel
inside. To request a model with measures against salt
damage, please consult the nearest sales office.
When installing the unit at a sandy place, make sure
that exhaust from the generator or radiator does not
blow the sand up in the air or into the machine.
A050507-1
In order to prevent from any persons other than those
engaged in the job site from using or interacting with
the machine, please prepare for safety fences around
the unit.
Safety Fence