3. Operation
3-17
3.6.3 Panel light
The control panel is equipped with an LED light. Turn the panel light switch [ON] to use.
When illumination is not necessary, turn the light [OFF]. If the machine is always operated with
the lamp switched [ON], the lamp life can be reduced.
3.6.4 Procedure of stopping
<Procedure>
1.
Power off of all connected loads.
2.
Set the Three-phase circuit breaker [A] and Single-phase circuit breaker [B] on the control panel of
the machine to [OFF] position.
3.
After about 5 minutes cooling down operation, turn the starter switch [C] to [STOP] position.
3.6.5 Operating procedures when engine fails to start up on first attempt
When the engine fails to start up even following the start-up procedures, do not keep the starter
running, but set the starter switch back to [STOP] and wait about 30 seconds. Then, repeat the
start-up procedure once again. If the repeated procedure does not allow the engine to run, the
following causes are suspected. Therefore, check the following:
No fuel
Clogging of the fuel filter
Discharge of battery (Low cranking speed)
3.6.6 Fuel line air bleeding device
If the machine runs out of fuel, bleed the air, according to the following procedures.
<Procedure>
1.
Replenish fuel.
2.
Turn the starter switch to [RUN] position.
Then the electric pump will start to automatically bleed air from the fuel pipes.
3.
Air bleeding will be completed within 20-30 seconds.