9
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Capacity Range Heat Pump Unit
Model No.
Nominal
Cooling
Capacity
(kW)
Nominal
Unit Input
Power
(kW)
EER
Nominal
Heating
Capacity
(kW)
Nominal Unit
Input Power
(kW)
EER
Dimensions
(H x W x L) mm
CUR092V16-1HP-0
14.6
4.4
3.32
13.7
5.1
2.69
1750 x 764 x 922
CUR092V20-1HP-0
21.1
6.7
3.15
19.4
7.2
2.69
1750 x 764 x 922
CUR092V25-1HP-0
26.5
9.3
2.85
24.2
9.1
2.66
1750 x 764 x 922
CUR092V29-1HP-0
28.7
10.6
2.71
26.4
10.2
2.59
1750 x 764 x 922
CUR122V35-1HP-0
39.7
13.7
2.90
35.5
14.3
2.48
1750 x 764 x 1222
CUR122V40-1HP-0
44.1
15.9
2.77
39.2
15.6
2.51
1750 x 764 x 1222
CUR092V16-VHP-0
16.4
4.9
3.35
15.0
5.5
2.73
1750 x 764 x 922
CUR092V20-VHP-0
21.0
6.8
3.09
19.4
7.2
2.69
1750 x 764 x 922
CUR092V25-VHP-0
25.3
8.4
3.01
23.2
8.8
2.64
1750 x 764 x 922
CUR092V29-VHP-0
28.4
10.4
2.73
26.5
10.3
2.57
1750 x 764 x 922
CUR122V35-VHP-0
38.1
13.1
2.91
34.4
13.6
2.53
1750 x 764 x 1222
CUR122V40-VHP-0
43.5
15.7
2.77
40.0
15.7
2.55
1750 x 764 x 1222
In cooling, 7°C evaporating, 35°C ambient (standard AC axial fan at maximum speed)
In heating, 50°C condensing, 5°C ambient (standard AC axial fan at maximum speed)
Input power includes compressor and fan