52
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Technical Data Heat Pump
Operational Limits
Typical Heating Application Envelope
28, -13
26, -15
28, 25
12, 25
12, -15
-20
-15
-10
-5
0
5
10
15
20
25
30
0
5
10
15
20
25
30
Return Air Temperature (°C)
Am
bi
en
t T
em
per
at
ur
e (
°C
)
CAUTION
A minimum air on temperature limit of 12°C must be adhered to ensure correct unit
operation.
Any fresh air introduced to the unit must have pre-heaters to maintain this minimum
temperature.
Operating Limits - Heat Pump Heating Cycle
-15, 25
-15, 38
25, 60
25, 25
13, 60
-20, 25
-20, 38
0
10
20
30
40
50
60
70
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
Ambient temperature (°C)
Co
nd
en
si
ng
te
m
pe
ra
tu
re
(°
C)
Fixed Capacity
Modulated Capacity
Data Based on a 12°C