59
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Electrical Data - Heat Pump Fixed Capacities
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.
CUR092V16-1HP-0
CUR092V20-1HP-0
CUR092V25-1HP-0
Unit Data
(1)
Nominal Run Amps
A
11
16
18
Maximum Start Amps
A
76
103
145
Recommended Mains Fuse Size
A
16
25
32
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor - Per Fan
Motor Type
AC
AC
AC
1~
1~
1~
Quantity x Motor Size
kW
1 x 0.6
1 x 0.6
1 x 0.6
Full Load Amps
A
2.6
2.6
2.6
Locked Rotor Amps
A
9.2
9.2
9.2
Compressor
Motor Size
kW
5
6
8
Nominal Run Amps
A
8
13
16
Locked Rotor Amps
A
70
100
142
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
11
16
18
Maximum Start Amps
A
48
63
88
Recommended Mains Fuse Size
A
16
25
32
Power Factor Correction
Nominal Run Amps
A
10
16
18
Maximum Start Amps
A
76
103
145
Recommended Mains Fuse Size
A
16
25
32
Compressor Nominal Run Amps
A
7.5
12.8
14.9
First upgrade EC Motor - Per Fan
1~
1~
1~
Quantity x Motor Size
kW
1 x 0.73
1 x 0.73
1 x 0.73
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF - Per Fan
1~
1~
1~
Quantity x Motor Size
kW
1 x 1.4
1 x 1.4
1 x 1.4
Full Load Amps
A
6.0
6.0
6.0
Locked Rotor Amps
A
18
18
18
CUR092V16-1HP-0 - CUR092V25-1HP-0
Condensing Unit
BluCube™
Te
ch
nic
al
Summary of Contents for BluCube CUR092V16-1CO-0
Page 90: ......