61
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Electrical Data - Heat Pump Fixed Capacities
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.
CUR092V29-1HP-0
CUR122V35-1HP-0
CUR122V40-1HP-0
Unit Data
(1)
Nominal Run Amps
A
20
26
30
Maximum Start Amps
A
145
163
202
Recommended Mains Fuse Size
A
32
40
50
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor - Per Fan
Motor Type
AC
AC
AC
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.6
1 x 1.97
1 x 1.97
Full Load Amps
A
2.6
3.4
3.4
Locked Rotor Amps
A
9.2
11.9
11.9
Compressor
Motor Size
kW
9.5
12.1
13.7
Nominal Run Amps
A
17
21
25
Locked Rotor Amps
A
142
158
197
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
20
26
30
Maximum Start Amps
A
88
100
124
Recommended Mains Fuse Size
A
32
40
50
Power Factor Correction
Nominal Run Amps
A
19
25
29
Maximum Start Amps
A
145
163
202
Recommended Mains Fuse Size
A
32
40
50
Compressor Nominal Run Amps
A
16.2
19.3
23.0
First upgrade EC Motor - Per Fan
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.73
1 x 1.85
1 x 1.85
Full Load Amps
A
3.3
2..85
2..85
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF - Per Fan
1~
N/A
N/A
Quantity x Motor Size
kW
1 x 1.4
N/A
N/A
Full Load Amps
A
6.0
N/A
N/A
Locked Rotor Amps
A
18
N/A
N/A
CUR092V29-1HP-0 - CUR122V40-1HP-0
Condensing Unit
BluCube™
Te
ch
nic
al
Summary of Contents for BluCube CUR092V16-1CO-0
Page 90: ......