50
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
BluCube
L1
¡
ç
Mains incoming supply 400V/3PH/50Hz
L2
¡
ç
L3
¡
ç
N
¡
ç
PE
¡
ç
502
¡
è
24 Volts AC
551
¡
ç
Cooling Signal
845
¡
ç
Variable Capacity Compressor Only
0-10 Volts Compressor demand
500
¡
è
0 Volts
561
¡
è
NO
Critical Alarm Normally Open
562
¡
è
Common
GND
563
¡
è
NC
Critical Alarm Normally Closed
Rx-Tx-
¡
ç
Use Awg20/22 twisted pair (with
overall shield) cable, Belden ref. 8762
(Airedale ref 6110316), or equivalent
for AireLan network
Network Connections (Inward connection)
Rx+Tx+
¡
ç
GND
¡
ç
Rx-Tx-
¡
è
Use Awg20/22 twisted pair (with
overall shield) cable, Belden ref. 8762
(Airedale ref 6110316), or equivalent
for AireLan network
Network Connections (Outward connection)
Rx+Tx+
¡
è
GND
¡
è
Interconnecting Wiring - Cooling Only
RxTx -
RxTx +
GND
RxTx -
RxTx +
GND
Panel Side
Customer Side
pLAN Termination
The plugged termination ensures that the connections are made simultaneously. Failure to attach the cables this way
may cause damage to the controller.