Section 4: Electrical Connections
Revision – August 2005
Page 4 - 9
4.4.1 Supervised Inputs
The system supports 2 supervised inputs from the customer interface. Supervised
inputs are analog inputs, which are monitored via a window comparator. These inputs
are monitored for normal operation, alarm type, and fault conditions.
A normally open switch is to be used as an input device. This switch must have a 750
ohm resistor in parallel with the contacts and a 1K ohm resistor in series with the
contacts. When the switch contacts are open the circuit will provide a signal, which
represents a normal operating condition. When the switch contacts are closed the
circuit will provide a signal which indicates an alarm condition. An open wire in this
circuit, or a short circuit, will produce an out of range signal, which indicates a circuit
fault.
Switch contacts must be rated for 20ma @ 24Vdc.
Summary of Contents for GASGUARD TE10
Page 2: ......
Page 12: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page i x...
Page 70: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page 3 4...
Page 92: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page 4 12...
Page 94: ......
Page 154: ......
Page 166: ......
Page 174: ......
Page 180: ......
Page 188: ......
Page 190: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 2...
Page 191: ...Appendix B Revision November 2004 Page B 3...
Page 192: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 4...
Page 193: ...Appendix B Revision November 2004 Page B 5...
Page 194: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 6...