Section 9: Troubleshooting
Revision – November 2004
9 - 5
9.2 No or Low Purge Gas Pressure
Possible Source of
Problem
Test
Solution
Closed purge gas supply
valve
Check position of supply
valve.
Open supply valve.
Purge gas supply pressure
regulator set incorrectly
Check setting on pressure
regulator.
Set pressure regulator to
correct delivery pressure
[80-90 psig (5.5-6.2
barg)].
Low purge gas cylinder
pressure
Check cylinder pressure.
Change cylinder.
Instrument nitrogen
supply not adequate to
open purge gas pneumatic
valves
Check instrument nitrogen
pressure.
Adjust to 85-95 psig
(5.9-6.6 barg) if
necessary.
Purge gas pressure
transducer(s)
malfunctioning
Check input to controller,
Check connections and
signal from pressure
transducers.
Repair connections,
repair or replace
transducer(s) as
necessary.
9.3 No or Low Purge Gas Flow
Possible Source of
Problem
Test
Solution
No or low purge gas
pressure
See Section 9.2 above.
Purge gas manual
isolation valve(s) closed
or partially closed
Check position of purge gas
manual isolation valve(s).
Open fully.
Are any purge vent valves
open?
Check position of all purge
vent valves.
Close any purge vent
valves if open.
Instrument nitrogen
supply not adequate to
open purge gas pneumatic
valves
Check instrument nitrogen
pressure.
Adjust to 85-95 psig
(5.9-6.6 barg) if
necessary.
Summary of Contents for GASGUARD TE10
Page 2: ......
Page 12: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page i x...
Page 70: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page 3 4...
Page 92: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page 4 12...
Page 94: ......
Page 154: ......
Page 166: ......
Page 174: ......
Page 180: ......
Page 188: ......
Page 190: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 2...
Page 191: ...Appendix B Revision November 2004 Page B 3...
Page 192: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 4...
Page 193: ...Appendix B Revision November 2004 Page B 5...
Page 194: ...GASGUARD TE10 Distribution System Manual Air Products and Chemicals Inc Page B 6...