VELTRON II
Air Monitor Corporation
116-011-98.P65 (8/30/10)
VELTRON II - IO&M Manual
4
3.5 – ALARM (option)
The VELTRON II Alarm Option provides the means for having the process signal compared to user selectable alarm
points and automatically activates a form C relay to generate dry contact alarm signal(s). User selectable alarm
configurations of Low/High, Low1/Low2, and High1/High2 plus Alarms On/Off, Setpoints, Dead Bands, and Delays are
configurable via the Operator Setup menu. Alarm Setpoints can be displayed on an Enhanced Display during
Normal
operating mode.
One choice among three alarm types are available to the user: Low/High; Low1/Low2; or High1/High2. An Alarm Delay
is available, if implemented (any time setting greater than zero), any condition that would normally cause an alarm,
triggers the delay timer first. If the alarm condition still exists after the delay times out, then the appropriate alarm
relay(s) are activated. The "Auxiliary Alarm On" LED will light whenever any alarm relay is activated. Alarm On/Off,
Type, Setpoints, Deadbands, and Delays are available and configurable using the Operator Setup menu. The Alarm
Setpoints can be displayed on the Enhanced Display during
Normal
operation.
High Alarm
Process Signal
High2 Alarm
Point
Point
Process Signal
Low1 Alarm
High1 Alarm
Point
Point
Low Alarm
Low2 Alarm
Process
Point
Point
Signal
Low/High Alarm
Low1/Low2 Alarm
High1/High2 Alarm
3.6 – SPECIAL FUNCTIONS (option)
When used in conjunction with an external input (second transmitter) applied to the special function input terminals, the
VELTRON II can perform one of the Special Functions listed below. Within the Operator Setup menu, both the external
input and the internal transmitter signals can be individually scaled to achieve a correct weighted basis. The resulting
Special Function output is available as an analog output and/or for the display on the optional Enhanced Display. When
% Deviation is selected as Special Function Type, contact closure is available for alarm/notification. Special Function
ON/OFF and Type are available and configurable using the Operator Setup menu.
%Deviation
. | EXTERNAL – INTERNAL | / | EXTERNAL |. This function has Alarm Setpoint, Deadband, and Delay that
are configurable via the Operator Setup menu. (If this function is selected, Alarm Option, Section 3.5, is not available.)
Summed Flow
. IN EXTERNAL
Averaged Flow.
(EX INTERNAL) / 2
Delta Flow, Internal - External
. INTERNAL – EXTERNAL
Delta Flow, External - Internal
. EXTERNAL – INTERNAL
Low Select
. Selecting the lesser of the INTERNAL and EXTERNAL signals.
High Select
. Selecting the greater of the INTERNAL and EXTERNAL signals.