VELTRON II
Air Monitor Corporation
116-011-98.P65 (8/30/10)
VELTRON II - IO&M Manual
SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION
This Main Menu selection is where all application specific data is entered to configure the VELTRON II for a unique
application. Data is entered under sub-menu, Process Configuration, and includes as applicable: Process Type,
Process Minimum/Maximum, Duct Area/Units, etc.
Note: Factory has entered data in this section based on customer supplied information. Data can be reviewed and
verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information sheet provided
with the unit. Review this information
BEFORE
making any changes, as they can have a significant effect on the
operation of the VELTRON II.
Under a second sub-menu, Calculator for Max Diff. Pres. or Flow, user can calculate either maximum flow or maximum
differential pressure (D.P.) when operating parameters have changed. Each Sub-menu will be addressed separately.
19
- Operator Password Selection
Trans. Scaling & Config.
- Low Pass Filter Selection
- Process Configuration
- Calc. for Max Diff Pres or Flow
1
- Return to MAIN MENU
Exits to Trans.
Scaling &
Configuration Menu
ON or OFF
Square Root
Off/On Selection
Square Root Off/On
ON
EXIT
Process Configuration
Transmitter Flow
or
Transmitter Velocity
Process Type
Selection
2
Process Type
TRANSMITTER FLOW
See UNITS list for
available selections
Process Units
Selection
Process Units
FLOW CFM
See FORMAT list for
available selections
Process Format
Selection
Process Format
FLOW XX,XXX CFM
Depends on Process
Type and Format
Process Minimum
Selection
Process Minimum
FLOW 0 CFM
Depends on Process
Type and Format
Process Maximum
Selection
Process Maximum
FLOW 10,000 CFM
Sq. Feet; Sq. Inches
Sq. Meters; or
Sq. Centimeters
Duct Area Units
Selection
3
Duct Area Units
Square Feet
3
0.00
to
325.00 Sq. Ft.
Duct Area
Selection
3
Duct Area
10.00 Sq Ft
°F, °C, °R or °K
Temperature Units
Selection
2
Temperature Units
°F
in.Hg, psia, kPa,
mbars or mm Hg
BarometrcPresUnits
Selection
2
Barometrc Pres Units
in.Hg
0% to 100.00%
in 0.01 increments
Output Lockdown
Selection
2
Output Lockdown
10.00% FS Output
1
Available only if Square Root is ON in
Process Configuration.
2 Available only if Square
Root is ON. If Square Root
is OFF, Process Type is
Differential Pressure (D.P.).
3 Available only if Process
Type is Transmitter Flow.
Available units depends on
Process Type selected.
Trans. Scaling & Configuration
Default selection shown.
Available selections:
Duct Area Range
0.00 - 325.00 Sq Ft
0.0000 - 3.2500
0.000 - 32.500
0.00 - 325.00
0.0 - 3250.0
Duct Area Range
Selection
3
Operator Setup Main Menu