VELTRON II - IO&M Manual
5.7 – OPERATOR PASSWORD SELECTION
User can select numeric password or bypass password requirement. Note: Units are shipped from the Factory with
the password set to 1,111 and bypassed.
1. While in Main Menu, use
UP
or
ON
to scroll to:
Operator Password
Selection
2. Press
ENT
to enter Operator Password Selection menu. Display will indicate:
Select Password
Selection
3. Press
ENT
and display will indicate current password (1,111).
4. Use
UP
or
DN
to change password. Once desired password is displayed, press
ENT
. New password will be
stored in memory and display will return to Operator Password Selection menu as in Step 2.
Note: If user desired not to change the password and return to Operator Password Selection menu, press
ESC
.
Unit will remain programmed as it was originally.
5. Use
UP
or
DN
to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Operator Password Selection menu and press
ENT
.
18
- EXIT Operator Setup
Operator Password Select
- Trans. Scaling & Config.
- Select Password Selection
- Bypass Password? Selection
- Return to Main Menu
Select Password
1,111
Bypass Password?
YES
NO or YES
0 to 9,999
Operator Password Selection
Return to
MAIN MENU
Default selection shown.
Available selections: