VELTRON II - IO&M Manual
38
SECTION 5 – OPERATION
5.17 – STANDARD DISPLAY CONFIGURATION (con't)
7. Use
UP
or
DN
to scroll to desired parameter. Press
ENT
and parameter will be stored in memory and display
will indicate as in Step 5.
Note: If user desires not to change the setting and return to Setup menu, press
ESC
. Unit will remain
programmed as it was originally.
8. If DIFF. PRESSURE was selected in Step 7 above, continue with Step 9.
If CUSTOM TEXT was selected in Step 7 above, continue with Step 16.
For all other parameters, proceed to Step 11.
9. Press
UP
and display will indicate:
LINE 2 D.P. UNITS
Selection
10. Press
ENT
and display will indicate current differential pressure units. Use
UP
or
DN
to change units and press
ENT
when desired units are displayed.
11. Press
UP
and display will indicate:
LINE 2 FILTER
Selection
Note: Filter selection will not be available if selected parameter is ALARM SETPOINT.
12. Press
ENT
and display will indicate current Filter setting selected for Line 2 [0 (None), 1 (Minimum), 2, 3, or 4
(Maximum)].
13. Use
UP
or
DN
to scroll to desired filter setting. Press
ENT
and filter setting will be stored in memory and display will
indicate as in Step 11.
14. Press
UP
and display will indicate:
Return to
MAIN MENU
15. Press
ENT
to return to Main Menu.
16. If Custom Text was selected in Step 7, press
UP
and display will indicate:
LINE 2 CUSTOM TEXT
Selection
17. Press
ENT
, display will indicate:
Cursor indicates position to be set.
There are 20 positions available to hold
custom text.
18. Use
UP
or
DN
to scroll through available characters (see ASCII Chart in Section 5.18 for available characters).
–