SECTION 5 – OPERATION
49
5.24 – TRANSDUCER CHARACTERIZATION SELECTION
Allows user to enter unique transducer characterization data when the transducer has been changed.
CAUTION
: – User should not make any changes to the data entered in the following menu items.
– This data has been entered by the Factory for the specific transducer installed in the unit.
– Only if the transducer is replaced by the user should new data be entered.
– This new data along with instructions will be provided with the new transducer from the Factory.
- Power Supply Calibration
Xdcr Characterizat'n Select
- Network Selection
- Data Point 1 Selection
- Data Point 2 Selection
- Data Point 3 Selection
- Data Point 4 Selection
- Data Point 5 Selection
- Return to MAIN MENU
Xdcr Character. Selection
Data Point 1
0
Data Point 2
2,500
Data Point 3
5,000
Data Point 4
7,500
Data Point 5
10,000
Return to
MAIN MENU
-250 to 250 in
increments of 1.
2250 to 2750 in
increments of 1.
4750 to 5250 in
increments of 1.
7250 to 7750 in
increments of 1.
9750 to 10250 in
increments of 1.
Default selection shown.
Available selections:
Operator Setup Main Menu